abaco systems' VME-3128A is designed to support 64 channels of differential or single-ended wide range (±25 mV to ±10 V) analog inputs.
One thousand and twenty-four dual-port Data Registers provide storage for continuous scanning of all channels. The scanning modes are executed automatically at powerup, system reset, or are entered under program control. The dual-port registers allow VMEbus access at any time to read the latest stored data.
Channel gain can be jumper selected as x1, x10, or x100, or can be software programmed individually for each channel. Scan rate is programmable up to 58 kCPS (thousand channels/s). Low pass input filters are available.
Features
- Continually digitizes all input channels and stores the results
- Program-selectable scanning of 16, 32, 48, or 64 channels
- 58 kHz conversion rate
- 14-bit A/D conversion
- 64 differential or single-ended inputs
Ordering Options
Please contact systerra for ordering options. Minimum Order Quantity: 10
|